Add to Cart
500sqmm AAC All Aluminum Conductor For Overhead Transmission Lines ISO 9001:2015
Applications
Stranded 1350 aluminum conductors shown in this section of data are classified as follows:
Class AA For bare conductors usually used in overhead lines.
Class A For conductors to be covered with weather-resistant materials and for bare conductors where greater flexibility is required.
Compact strand conductor for use in bare overhead applications or for use with weather-resistant coverings or insulations is also available.
Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.
Construction
Aluminum alloy 1350-H19 wires, concentrically stranded.
STANDARD
ASTMB231,BS215 Part1,DIN48201,IEC61089
IEC 61089
Specification No.
| Nominal cross section mm²
| No.of single wire
| Diameter mm | Unit length weight kg/km
| Rating tension resistance kN
| DC resistance 20℃ Ω/km
| |
Single wire | Stranded wire | ||||||
10 16 25 40 63 | 10 16 25 40 63 | 7 | 1.35 1.71 2.13 2.7 3.39 | 4.05 5.12 6.40 8.09 10.2 | 27.4 43.8 68.4 109.4 172.3 | 1.95 3.04 4.50 6.80 10.39 | 2.8633 1.7896 1.1453 0.7158 0.4545 |
100 125 160 200 250 | 100 125 160 200 250 | 19
| 2.59 2.89 3.27 3.66 4.09 | 12.9 14.5 16.4 18.3 20.5 | 274.8 343.6 439.8 549.7 687.1 | 17.00 21.25 26.40 32.00 40.00 | 0.2877 0.2302 0.1798 0.1439 0.1151 |
315 400 450 500 560 | 315 400 450 500 560 | 37 | 3.29 3.71 3.94 4.15 4.39 | 23.0 26.0 27.5 29.0 30.7 | 867.9 1102.0 1239.8 1377.6 1542.9 | 51.97 64.00 72.00 80.00 89.60 | 1.0916 0.0721 0.0641 0.0577 0.0515 |
630 710 800 900 1000 | 630 710 800 900 1000 | 61 | 3.63 3.85 4.09 4.33 4.57 | 32.6 34.6 36.8 39.0 41.1 | 1738.3 1959.1 2207.4 2483.3 2759.2 | 100.80 113.60 128.00 144.00 160.00 | 0.0458 0.0407 0.0361 0.0321 0.0289 |
1120 1250 1400 1500 | 1120 1250 1400 1500 | 91 | 3.96 4.18 4.43 4.58 | 43.5 46.0 48.7 50.4 | 3093.5 3452.6 3866.9 4143.1 | 179.2 200.00 224.00 240.00 | 0.0258 0.0231 0.0207 0.0193 |
Why you choose us?